Shenzhen Liruisi Electronics Co., Ltd.

Shenzhen Liruisi Electronics Co., Ltd.

Manufacturer from China
Verified Supplier
3 Years
Home / Products / Lead Acid Batteries /

Communication Uninterruptible Power Supply Batteries 2V 500Ah Valve Regulated Sealed

Contact Now
Shenzhen Liruisi Electronics Co., Ltd.
Visit Website
City:shenzhen
Province/State:guangdong
Country/Region:china
Contact Person:MsKelly
Contact Now

Communication Uninterruptible Power Supply Batteries 2V 500Ah Valve Regulated Sealed

Ask Latest Price
Video Channel
Brand Name :LIRUISI
Model Number :LT-500
Place of Origin :China
MOQ :1 set
Price :negotiation
Payment Terms :L/C, D/A, D/P, T/T, Western Union, MoneyGram
Supply Ability :9999 units
Delivery Time :8 working days
Usage :UPS
Sealed type :Sealed
Maintenance type :Free
Application :UPS
Battery type :Sealed VRLA Deep Cycle Gel Lead Acid Battery
Electrolyte :Sulfuric Acid Gel
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

LIRUISI Communication Battery 2V Valve Regulated Sealed Lead-Acid Battery LT-500

Product introduction:

UPS (Uninterruptible Power Supply) lead-acid battery is a battery mainly used for power backup and is usually installed in UPS systems to provide power continuity performance. This kind of storage battery can store a large amount of energy, and when the grid voltage is unstable or there is a power failure, it will start working immediately, automatically providing backup power for computers, servers, communication equipment and other important loads, so as to ensure the normal operation and use of equipment.

LT series 2V valve regulated sealed lead-acid battery series product specifications:

Model standard voltage capacity(Ah) size(mm)
10HR 10HR Length (L) Width (W) High (H) TH Weight (kg)
LT-500 2 500 325 243 243 328 365 37

Installation, use and maintenance

Battery charging:

1. Float charge (limit voltage, control current) use: charging voltage 2.275-2.30V/single cell, temperature compensation, temperature compensation coefficient per unit is 3mv (based on 20)

2. When trickle is used, the battery float charge current is high speed to less than 2Ma/Ah

3. Cycle use (full and stop, discharge and charge): charging voltage 2.35-2.45V/single cell

4. The maximum current shall not exceed 25% of the nominal capacity

Note: The battery should not be used in a closed or high temperature environment and should be kept away from fire

Connection of batteries:

1. Batteries or battery packs with the same actual capacity can be used in series

2. Cells or battery packs with the same actual voltage can be used in parallel

3. The connection part should be tight to prevent sparks; If the contact is poor, the contact surface can be cleaned with soda

4. The positive and negative poles shall not be reversed or short-circuited