Add to Cart
LIRUISI modular high frequency UPS uninterruptible power supply N series 600KVA
Product introduction:
LIRUISI's N series three-in, three-out UPS adopts modular design and N+X parallel redundancy technology, and the product capacity covers each power segment between 50kVA and 600kVA, which is convenient for users to flexibly configure and gradually invest. This series of UPS can almost completely solve all power supply problems, such as power failure, mains high voltage, mains low voltage, voltage instantaneous drop, amplitude reduction oscillation, high voltage pulse, voltage fluctuation, surge voltage, harmonic distortion, clutter interference, frequency fluctuation and other power supplies.
Modular high-frequency uninterruptible power supply (UPS) is a highly efficient and reliable power equipment with modular design, which can flexibly configure output voltage and current according to user needs.
way of working:
Three-in, three-out/three-in, single-out, double-conversion online work modular model operation.
Product Features:
N50-600kVA is a three-in, three-out modular UPS launched by our company, the product adopts digital control, modular design and N+X parallel redundancy technology. The product capacity covers each power segment between 50kVA and 600kVA, which is convenient for users to flexibly configure and gradually invest. Can be 4 parallel to 2400kVA modular UPS-N series 50-600KVA UPS This series UPS is high-power three-in, three-out UPS power supply, 20-300KVAUPS, N60KVA/90KVA, N100KVA/150KVA, N200KVA/300KVA output can be connected to a completely unbalanced load, when the output is connected to an unbalanced load, the input current is balanced in three phases, which can balance the load of the three-phase power grid.Digital control, high power density modular design, 19-inch standard cabinet, N+X parallel redundancy, intelligent battery management, LCD color screen display, safe and convenient maintenance, intelligent managementThree-in, three-out pure online double-conversion product, supporting 380/400/415V, 50/60Hz power grid system, providing the best power supply quality and load protection.The rectifier adopts IGBT, with PFC function, input power factor up to 0.99, input harmonic current less than 3%, and the efficiency of the whole machine is ≥ 94.5%, which is green and environmentally friendly, high efficiency and energy saving.Fully digital dual DSP control.
N50KVA-N600KVA【Modular HF UPS System】 | ||
Model | N00KVA | |
rated capacity | cabinet | 50k-600k / |
(VA/W) | 50k-600k / | |
module | 50k / 50k | |
(VA/W) | ||
Maximum module | 12 | |
quantity | ||
N50KVA-N600KVA [modular high-frequency UPS system] technical parameters | ||
UPS input | Rated input voltage (Vac) | 380/400/415 |
Input voltage range (Vac) | 138~485Vac; 305~485Vac does not derate, 138~305Vac linear derating | |
Wiring system | Three-phase five-wire | |
Input frequency range (Hz) | 40-70 | |
Input power factor | ≥0.99 | |
Input current harmonics (THDi) | ≤ 3% (100% linear load) | |
bypass input | Rated input voltage (Vac) | 380/400/415 |
Input voltage range (Vac) | 220 Limit: 25% (optional +10%, +15%, +20%) 230 Upper limit: 20% (optional +10%, +15%)240 Upper Limit: 15% (optional +10%) Lower limit: -45% (optional -10%, -20%, -30%) | |
Wiring system | Three-phase five-wire | |
Bypass sync tracking range (Hz) | ±10% | |
UPS output | Output voltage (Vac) | 380/400/415±1% |
power factor | 1 | |
overload capacity | 110% load, turn bypass after 60min; 125% load, turn bypass after 10min; 150% load, for 1 min and then turn to bypass | |
Switch time (ms) | 0 | |
battery | battery voltage | ±180V/±192V/±204V/±216V/±228V/±240/±252/±264/±276/±288/±300Vdc (Section 30/32/34/36/38/40/42/44/46/48/50); (30 knots ~ 50 knots optional, default 36 knots, 36 knots and 50 knots output power is not derating; Output power derating to 0.9 at 32 and 34 cells, 0.8 output power at 30 cells) |
size | UPS cabinet | 1200×850×2000 |
module | 440×620×130 | |
weight | UPS cabinet | 400 |
module | 33 |